P100-1

With a reputation for quality within our already successful 50 – 218 kVA power range. Our redesigned range confirms our position as a global leader in the design and manufacture of generator sets and demonstrates our commitment to continuous product improvement. Our latest product development sees us introduce bold new enhancements. Every single model in the new range has been Designed to Deliver More…offering improved performance, durability and serviceability. The new 50 – 218 kVA range offers you outstanding value for money and in turn guarantees maximum efficiency and productivity.
P100-1
  • Features
  • Specifications
  • Suggested Products

FG WILSON DIESEL ENGINE

Perkins Engine

 

ALTERNATOR

Benefiting from a choice of leading alternators, the range incorporates the Marelli alternator as standard across three phase models.

 

DCP10

The FG Wilson DCP range allows you to monitor and control your generator set with ease, providing important diagnostic information whilst ensuring your unit operates within safe parameters. FG Wilson DCP digital control panels, provide simple, intuitive menu navigation and control of your generator set operations. Key information is displayed via the LCD screen and LED’s using universally recognised symbols, eliminating the need for complex instructions or language settings.

 

DESIGN CRITERIA

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

 

SINGLE-SOURCE SUPPLIER

Fully prototype tested with certified torsional vibration analysis available

 

WORLD WIDE PRODUCT SUPPORT

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

If you have any questions regarding this product, call us on 0203 259 0100, or email us

Generator Set Specifications

Minimum Rating
80.0 kVA / 64.0 kW
Maximum Rating
100.0 kVA / 80.0 kW
Frequency
50 Hz or 60 Hz
Speed
1500 or 1800 RPM
50 Hz Prime
80.0 kVA / 64.0 kW
50 Hz Standby
88.0 kVA / 70.4 kW
60 Hz Prime
90.0 kVA / 72.0 kW
60 Hz Standby
100.0 kVA / 80.0 kW

Generator Set Configurations

Emissions/Fuel Strategy
Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Engine Specifications

Engine Model
Perkins® Perkins 1104A-44TG2
Bore
105 mm (4.1 in)
Displacement
4.4l (268.5 cu. in)
Stroke
127 mm (5 in)
Compression Ratio
17.25:1
Governor Type
Mechanical
60 Hz Prime
90.0 kVA / 72.0 kW
60 Hz Standby
100.0 kVA / 80.0 kW

If you have any questions regarding this product, call us on 0203 259 0100, or email us

Enclosures

Robust, weatherproof and soundproof enclosures for all generator sizes and all market sectors, including residential applications.

Control Panels

Choose from keystart, automatic, digital or synchronising; all of our control panel systems are safe and easy to use.

If you have any questions regarding this product, call us on 0203 259 0100, or email us