P2000-1/P2001E

Proven in the field, this range of generator sets are capable of providing reliable power for critical applications including: mini power stations, data centres, large factories, airports, hospitals, large retail stores, and the financial sector. A 50˚C package option is available to ensure efficient operation in high ambient temperatures. Custom-built weatherproof and acoustic enclosures can be tailored to suit any application. Providing personnel access and separate components for cooling, they make generator set installation and maintenance as quick and easy as possible.
P2000-1/P2001E
  • Features
  • Specifications
  • Suggested Products

FG WILSON DIESEL ENGINE

Perkins Engine

 

ALTERNATOR

Benefiting from a choice of leading alternators, the range incorporates the Marelli alternator as standard across three phase models.

 

POWERWIZARD 1.1+

The FG Wilson PowerWizard range of digital control panels, combine straightforward menu navigation with advanced metering and protection technology. They are used in automatic mains failure applications in conjunction with transfer panels. Our PowerWizard range allows you to monitor and control your generator set with ease, whilst ensuring your unit operates within safe parameters and provides important diagnostic information when needed.

 

DESIGN CRITERIA

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

 

SINGLE-SOURCE SUPPLIER

Fully prototype tested with certified torsional vibration analysis available

 

WORLD WIDE PRODUCT SUPPORT

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

If you have any questions regarding this product, call us on 0203 259 0100, or email us

Generator Set Specifications

Minimum Rating
1850.0 kVA / 1480.0 kW
Maximum Rating
2000.0 kVA / 1600.0 kW
Frequency
50 Hz
Speed
1500 RPM
50 Hz Prime
1850.0 kVA / 1480.0 kW
50 Hz Standby
2000.0 kVA / 1600.0 kW
60 Hz Prime
- / -
60 Hz Standby
- / -

Generator Set Configurations

Emissions/Fuel Strategy
Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Engine Specifications

Engine Model
Perkins® 4016-61TRG1
Bore
190 mm (7.5 in)
Displacement
61.1l (3730.0 cu. in)
Stroke
190 mm (7.5 in)
Compression Ratio
13.0:1
Governor Type
Electronic
60 Hz Prime
- / -
60 Hz Standby
- / -

If you have any questions regarding this product, call us on 0203 259 0100, or email us

Enclosures

Robust, weatherproof and soundproof enclosures for all generator sizes and all market sectors, including residential applications.

Control Panels

Choose from keystart, automatic, digital or synchronising; all of our control panel systems are safe and easy to use.

If you have any questions regarding this product, call us on 0203 259 0100, or email us